Appendix J: Troubleshooting
Table J1: HRV600i, 700i and 1200i Troubleshooting
Symptoms Possible Causes Solutions
Inside air is too dry.
Over ventilation – speed setting too high. Adjust speed setting.
Dehumidistat setting too low.
Set dehumidistat control in a higher position (if
applicable).
Persistent condensation on windows,
walls, ceilings, etc.
Improper adjustment of dehumidistat control.
Adjust dehumidistat control knob to a lower
setting.
Improper ventilation rate. Install a dehumisistat (option).
Window frame is too cold or leaky. Repair window frame.
Unit stops functioning. Electrical supply interrupted. Check the unit circuit breaker.
Air from supply diffusers too cold.
Imbalance of supply and exhaust air.
Check filters and heat exchangers for blockage.
Check balance of airflows.
Outdoor temperature very cold. Install electric duct heater if necessary.
Unit makes annoying noise. Blower wheel out of alignment.
Remove the motor/blower assembly and adjust
blower wheel.
Heat exchanger freezing up.
Imbalance of supply and exhaust air.
Check filters and heat exchangers for blockage.
Check balance of airflows.
Frost control damper not functioning.
Check for operation of both frost control
damper actuators.
Low exhaust airflow in winter season.
Heat exchanger flutes are positioned in the
exhaust airstream.
Remove flat plate heat exchanger sections and
re-position the flute side of the heat exchanger
into the supply airstream.